Air-to-Air Sizing Program

(Note: Sun Loading Not Included in Calculations.)

Instructions

  1. Size your cabinet. Obtain the dimensions in inches.

  2. Enter height, width and depth accordingly.

  3. Enter number of exposed sides of cabinet. In other words, is the cabinet up against the wall or another cabinet?
    Example: if your cabinet is on the floor and up against the wall, there will only be 4 sides exposed - front, both sides and the top.

  4. Calculate the heat loss in watts or heat load.

  5. Enter data in defined fields.

  6. Click the calculate button.

  7. The program will display the calculated temperature performance using that particular cabinet model.

    All drop-in and flush mounts models are listed with their efficiency rating and calculated sizing results.

 Click here to start program 

 Sample sizing:

 h = 72, w = 36, d = 24

 watts = 700

 5 sides exposed (cabinet mounted on wall) 

 Using a CC2000 = approx. 9°F. If ambient temp = 75°F then the inside temp in the cabinet would be 86°F.